Products
| Article number | 040-8-0064 |
| Operating principle |
For carbon dioxide: Non-dispersive infrared (NDIR) For carbon monoxide: Fuel type electrochemical gas sensor with temperature compensation |
| Measured gas | CO, CO₂ |
| Measurement range | 0–3% |
| Operating range RH | 5 - 85 % RH |
| Operation range °C | <50 °C |
| Warm-up time | TBA |
| Response time | <3 min |
| Power supply | 24 V AC |
| Peak current | |
| Average current | <3 W |
| Communication | Modbus protocol, UART |
| Outputs | 0/2 to 10 VDC or 0/4-20mA (CO) |
| Outputs | 0/2 to 10 VDC or 0/4-20mA (CO2) |
| Compliance | |
| Maintenance | Maintenance free |
| Life expectancy | >5 years |
| Dimensions | 150 x 85 x 46 mm (L x W x H) |
| Weight | |
| Storage conditions | -40-70 °C |
| Accuracy (CO2 ) | ±30 ppm ±3% of reading |
| Accuracy (CO) | ±10 ppm |
Disclaimer : Please refer to product specification for the complete technical details.
| Article number | Product | Description |
| 040-8-0064 | aSENSE MIII | CO and CO₂ sensor ventilation controller |
| 040-8-0066 | aSENSE MIII Duct Disp | CO and CO₂ sensor ventilation controller with display |
aSENSE MIII
- aSENSE MIII Product Sheet
- aSENSE MIII Installation Manual
- aSENSE MIII Duct Installation Manual
- aSENSE MIII User Manual
- aSENSE MIII Product Specification