Products
| Article number | 004-0-0053 |
| Operating principle | Non-dispersive infrared (NDIR) |
| Measured gas | CO₂ |
| Measurement range | 400–10 000ppm |
| Accuracy | ±40 ppm ±3% of reading1 |
| Operating range RH | <85 % RH |
| Operation range °C | <50 °C |
| Warm-up time | <60s |
| Response time | ≤30s |
| Power supply | 4.5 - 5.25 V |
| Peak current | 300 mA |
| Average current | 18mA |
| Communication | Modbus protocol, UART |
| Outputs | Digital |
| Compliance | ANSI/ASHRAE Standard 62.1-2022, RESET Standard Grade B, WELL Building Standard® (WELL v2™) |
| Maintenance | Maintenance free |
| Life expectancy | >15 years |
| Dimensions | 33.9 x 19.8 x 8.7 mm (L x W x H) |
| Weight | 8 g |
| Storage conditions | -40–70 °C |
- ±75ppm Accuracy at 600, 1000 and 2500ppm @ sea level, 77 °F (25 °C) (ANSI/ASHRAE compliance)
| Article number | Product | Description |
| 004-0-0013 | S8 Residential | Versatile CO₂ sensor for residential applications |
| 004-0-0050 | S8 2% | For high CO2 concentrations |
| 004-0-0010 | S8 Commercial | Miniature, low power and versatile sensor for CO₂ sensing |
| 004-0-0056 | S8 Residential Pin Header | For connection by pin headers (for ventilation control and CO2 monitoring) |
| 004-0-0017 | S8 5% | For very high CO2 concentrations |
| 004-0-0053 | S8 LP | For applications where both energy consumption and accuracy are critical factors |
S8 LP
S8 Residential
S8 Commercial
Technical Description
Handling Manual
Senseair Development kit
Product Compliance
| Article number | Product | Description |
| 00-0-0101 | SADK S8 & S88 | Senseair Development kit for S8 & S88. |